Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | HPM1106-30KVA | HPM1110-50KVA | HPM3106-30KVA | HPM3110-50KVA | HPM3110-100KVA | HPM3320-60KVA | HPM3320-100KVA | HPM3320-200KVA | |
Capacity (VA/Watts) | UPS cabinet | 6~30k / 4.8~24k | 6~50k / 4.8~40k | 6~30k / 4.8~24k | 6~50k / 4.8~40k | 6~100k / 4.8~80k | 10~60k / 9~54k | 10~100k / 9~90k | 10~200k / 9~180k |
HPM module | 6k / 4.8k, 10k / 8k | 10k / 9k, 15k / 13.5k, 20k / 18k | |||||||
INPUT | |||||||||
Nominal voltage | 220/230Vac | 380/400Vac (3Ph+N+PE) or 220/230Vac | 380/400/415Vac, (3Ph+N+PE) | ||||||
Operating voltage range | 120~276Vac | 208~478Vac or 120~276Vac | 208~478Vac for half load; 305~478Va c for full load | ||||||
Operating frequency range | 40~70Hz | ||||||||
Power factor | ≥0.99 | ||||||||
Harmonic distortion (THDi) | 5%(100% non-linear load) | 2%(100% non-linear load) | |||||||
Bypass voltage range | 220Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 230Vac Max.voltage: +20% (optional +10%,+15%) 240Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
380Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 400Vac Max.voltage: +20% (optional +10%,+15%) 415Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
|||||||
Bypass frequency range | Frequency synchronize tracing range:±10% | ||||||||
Generator access | Support | ||||||||
OUTPUT | |||||||||
Rated voltage | 220/230Vac | 380/400/415Vac(3Ph+N+PE) | |||||||
Power factor | 0.8 | 0.9/1(Customized) | |||||||
Voltage regulation | ±1% | ||||||||
Frequency | Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |||||||
Bat. mode | (50/60±0.1%)Hz | ||||||||
Crest factor | 3:1 | ||||||||
Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load |
||||||||
Efficiency | 93.50% | 95.50% | |||||||
BATTERY | |||||||||
Battery voltage | ±96/±108/±120Vdc; Battery quantity(optional) | ±192/±204/±216/±228/±240Vdc; Battery quantity(optional) | |||||||
Charging current(A) | UPS cabinet | 30A (Max.) | 60A (Max.) | 30A (Max.) | 60A (Max.) | 18A (Max.) | 30A (Max.) | 60A (Max.) | |
HPM module | 6A (Max.) (Charge current can be set according to battery capacity installed) | ||||||||
Backup time | Depends on the capacity of external batteries | ||||||||
SYSTEM FEATURES | |||||||||
Transfer time | Utility to battery:0ms; Utility to bypass:0ms | ||||||||
Overload | Line mode | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately | |||||||
Bat. mode | Load≤110%: last 30S,≤125%: last 1S,≤150%: last 200ms,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 1S,≥150% shut down UPS immediately | |||||||
Bypass mode | Breaker (6kVA:40A / 10kVA:60A) | Breaker (10kVA:20A / 15kVA:32A / 20kVA:40A) | |||||||
Short circuit | Hold whole system | ||||||||
Noise suppression | Complies with EN62040-2 | ||||||||
Communication interface | UPS cabinet : RS232, RS485, Dry contact, Intelligent slot x 2(SNMP card,Relay card optional); HPM series UPS module: RS232 |
||||||||
ENVIRONMENT | |||||||||
Operating temperature | 0~40ºC | ||||||||
Storage temperature | -25~55ºC | ||||||||
Humidity range | 0~95% (Non-condensing) | ||||||||
Altitude | <1500m. When >1500m, derating power for use | ||||||||
Noise level | <55dB | <65dB | |||||||
PHYSICAL | |||||||||
Dimension D×W×H (mm) | UPS cabinet | 840×600×1400 | 840×600×2000 | 840×600×1400 | 840×600×2000 | 840×600×1400 | 1100×600×2000 | ||
HPM module | 443x580x131 (3U) | ||||||||
Net weight (kg) | UPS cabinet | 138 | 150 | 138 | 150 | 213 | 149 | 152 | 290 |
HPM module | 6kVA/23; 10kVA/25 | 10kVA/26; 15kVA/30; 20kVA/31 | |||||||
STANDARDS | |||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
Adopting digital control design, and the control system is more reliable
High power density design, capacity of single power module is 6KVA/ 10KVA/ 15KVA/ 20KVA/ 25KVA/ 30KVA/ 40KVA, the height of all these modules is 3U.The power of system ranged from 6KVA to 520KVA corresponds to the number of parallel power modules from 1 to 13
Redundant control system, each power module is equipped independent control system, and control itself independently according to the sharing message, and the fault module separates from the system automatically
Support parallel expansion for cabinet, and parallel expansion is up to 4 cabinets.
Voltage of batteries can be configured flexibly, 1 input 1 output/ 3 input 1 output ±96Vdc/ ±108Vdc/ ±120Vdc(16/18/20PCS)selectable; 3 input 3 output±216Vdc/±228Vdc/±240Vdc (32/34/ 36/38/40PCS) selectable
Intelligent charging mode, Charging current can be configured , there are 3 charging mode which are constant current mode,constant voltage mode,floating charging mode, and the charging mode can be transfer smoothly.
Wuhan Unique Mechanical And Electrical Equipment Co., LTD. is a high-tech enterprises with a combination of of science, industry and trade. We mainly engaged in R&D and manufacturing of network center room equipment, such as PDU, ODF, CMA, Fiber Spool Frame, Network Panel, Network Cabinet, OF Jointing Box, Fiber Optic Connector, ADSS Cable, Micro Fiber, Pigtail, Patch Cord, UTP Cable, etc. Provide high level of technical consultation and technical services.