Phase: | Single Phase |
---|---|
Type: | On-line |
Protection: | Overvoltage |
Application: | Communication |
Classification: | Lighting/Power |
Standby Time: | Long-acting Machine |
Customization: |
---|
Suppliers with verified business licenses
UPS5000-E Battery Integrated Solution features the double-conversion online and modular design with pre-integrated battery module, fast on-site deployment & installation, intelligent management, unattended operation and simple O&M, thus providing customers with reliable, efficient and simple modular UPSs.
Scenarios
• Small-to-medium sized data centers.
• Telecom and Internet switch computer rooms of small-to-medium sized enterprises.
• Area network and communication equipment rooms.
• Computer rooms of branch offices of industries like finance, etc.
Features
Reliable
• Wide input voltage range from 138Vac to 485Vac to suit for worst grid and minimize battery use.
• Dual-controller design to eliminate the single point of failure.
• Redundant auxiliary power supply and fans.
• Intelligent Battery Management: monitoring battery's temperature, early warning for failure, battery powered high reliability.
Efficiency
• High efficiency of system up to 96%.
• Intelligent hibernation technology to keep UPS operating at high efficiency.
• All in one design, saving the area of 50%.
Simple
• Modularized power, bypass, control and battery modules, fast installation and maintenance.
• 7-inch colored LCD showing real-time operation status in various languages.
• Various communication interfaces including dry contacts, RS485, Modbus etc.
• NetEco network manager, supporting centralized management to all the UPSs
Specifications
Model | UPS5000-E-(25-75kVA)-FM | ||||
Capacity (kVA/kW) | 25kVA/kW | 50kVA/kW | 75kVA/kW | ||
Input | Mains | Rated Voltage | 380/400/415Vac | ||
Voltage Range | 138 to 485Vac | ||||
Input Wiring | 3Ph+N+PE | ||||
Frequency Range | 40 to 70 Hz | ||||
Total Harmonic Distortion | <3% (100% linear load) | ||||
Input Power Factor | 0.99 | ||||
Bypass | Rated Voltage | 380/400/415Vac | |||
Frequency Range | 50/60Hz (adjustable, 0.5 to 6Hz, ±2Hz by default) | ||||
Input Wiring | 3Ph+N+PE | ||||
Output | Rated Voltage | 380/400/415Vac | |||
Output Frequency | Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery mode) | ||||
Output Power Factor | 1 | ||||
Waveform | Sine wave; THDv<1% (linear load) | ||||
Output Wiring | 3Ph+N+PE | ||||
System Efficiency | Up to 96% | ||||
Overload Capacity | ≤110% overload for 60min; ≤125% overload for 10min; ≤150% overload for 1min | ||||
Environment | Operation Temperature | 0 to 40 ºC | |||
Storage Temperature | -40 to 70 ºC | ||||
Relative Humidity | 0% to 95% (No condensing) | ||||
Maximum Operation Altitude | 0-1000m. Above 1000m, derating rate based on EN/IEC 62040-3 | ||||
Noise | <65dB | ||||
Others | System Expandability | 4 | |||
Integrated Cabinet Power Backup | Standard configuration 2 to 4 groups of battery (8 to 16 battery modules) | ||||
Battery Cabinet (optional) Power Backup | Optional battery cabinet, 1 to 8 groups of battery (4 to 32 battery modules) per cabinet, max. 4 cabinets in parallels | ||||
Battery Module | Support battery or empty battery for battery module, battery typical configuration: 10×12V 9Ah | ||||
Height×Width×Depth (mm) | 2000 × 600 × 1100 | ||||
Weight (full configuration) | 890kg | 910kg | 930kg | ||
Certifications | EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE; CB; RoHS, REACH, WEEE, etc. | ||||
Communications | SNMP, RS485, Dry contacts etc. |
Notice
1. The UPS series are for commercial/industrial use and not used for life support equipment;
2. The critical systems concerning economic and public security must adopt power supply architecture that comply with Uptime TIER III or TIER IV requirements stated in TIA942.