| Customization: | Available |
|---|---|
| Usage: | Telephone, Computer, Workstation, Server |
| Type: | Wired |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Since setting the new standard for rectifier efficiency, the Flatpack2 HE family is now available in a variety of voltages and power ratings, all with superior efficiency up to 96.5%.
With more than 4 billion in-field operating hours and a proven cumulative field MTBF of more than 1,9 million hours, Flatpack 2 HE is the only HE (High Efficiency) rectifier with a proven track record.
The line of systems available for Flatpack2 HE 48V rectifiers spans from 8kW 2U racks with complete distribution to multi-cabinet systems in multi MW installations.
Applications
Telecom - Mobile / Wireless
•radio Base Stations/ Cell Sites
•lte / 4g / Wimax
•mobile Switching Center (msc)
•microwave
•broadband Telecom - Fixed
•central Office
•telephony Servers / Switches
•fiber Optics
•microwave
•broadband
•datacenters
Power Utilities
•scada
Key Features
•proven Reliability
•high Efficiency (he)
•power Dense, Up To 33 W/inch3
•wide Temperature Range
•application Flexibility 2kw
•global Compliance (ce, Ul)
•patented He Technology
Specification
| Model | 48V / 2000W HE | 48V / 3000W HE | |
| Part number | 241115.105 | 241119.105 | |
| INPUT DATA | |||
| Voltage (nominal) | 185 - 275 VAC / 185 - 275 VDC | 176 - 277 VAC | |
| Voltage (range) | 85 - 300 VAC / 85 - 275 VDC | 85 - 305 VAC | |
| Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz | 45 - 66 Hz | |
| Current (maximum) @ nominal input, full load | 11.6 ARMS | 19.2 ARMS | |
| Protection | Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC | Fuse in both lines Varistor for transient protectionDisconnect above 305 VAC | |
| OUTPUT DATA | |||
| Voltage (default) | 53.5 VDC | ||
| Voltage (adjustable range) | 43.5 - 57.6 VDC | 43.5 - 583) VDC | |
| Power (maximum) | 2000 W | 3000 W | |
| Power @ 85 VAC | 850 W | 1380 W | |
| Current (maximum) @ nominal input, full load | 41.7 A | 62.5 A | |
| Ripple, 30MHz bandwidth | < 100 mVpp | < 150 mVpp | |
| Psophometric noise | < 2 mVRMS | < 2 mVRMS | |
| Static Voltage regulation | ±0.5% for 10 - 100% load | ||
| Dynamic Voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms | ||
| Protection | Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting | ||
| OTHER SPECIFICATIONS | |||
| Efficiency @ nominal input | 96 % | ||
| Isolation | 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth | ||
| Alarms: Red LED 'on' | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure | ||
| Warnings: Yellow LED 'on' | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage | ||
| Normal (module running): Green LED 'on' | |||
| Acoustic noise, full load @ Tambient = 25°Cfull load @ Tambient = 40°C | < 20 dBA< 56 dBA | < 40 dBA< 58 dBA | |
| MTBF (Telcordia SR-332 Issue I method III (a)) | >350 000 (@ Tambient : 25 °C) | >300 000 (@ Tambient : 25 °C) | |
| Operating temperature | -40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing | ||
| Temperature de-rating | >55°C (131°F), 1200W @ 75°C (167°F) | >55°C4) (131°F), 2100W @ 75°C (167°F)4) | |
| Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | ||
| Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs) | ||
| DESIGN STANDARDS | |||
| Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013 | ||
| EMC | EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE | ||
| Marine | DNVGL-CG-03392) | - | |
| Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised | ||
| power derating, maximum 1000W @ 230Vac 16 2/3 Hzonly valid for part number 241115.105M | 57.6V for HW revision ≤ 5 from HW revision 6: shutdown at 95°C with de-rating to ~1000W | ||
| 1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
| 2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
| 3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
| 4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
| 5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
| 6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
| 7 | Rectifier module | Huawi | R4850N1 | |
| 8 | Rectifier module | Huawi | R4850G1 | |
| 9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
|
| 10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
|
| 11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
|
| 12 | Rectifier module | Eaton | APR24-3G | |