Customization: | Available |
---|---|
Output Type: | Multiple |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Compact HE 1U power systems
Increasing network speed demands flexible and expandable DC powersolutions. Due to its small size, high efficiency, reliability and wide range ofcommunication, the Flatpack S System is the key for future needs. The shallow depth makes the system suitable for most cabinets and thereby excellent as a replacement unit.
Applications
Telecom - Mobile / Wireless
Radio Base Stations/ Cell
Sites
Lte / 4g / Wimax
Distributed Antenna
Systems
Microwave
Broadband
Telecom - Fixed
Telephony Servers /
Switches
Fiber Optics / Fttx
Microwave
Cable
Broadband
Flatpack s 1u systems 1u x 19" 48v - 2r/3r
1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
7 | Rectifier module | Huawi | R4850N1 | |
8 | Rectifier module | Huawi | R4850G1 | |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
|
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
|
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
|
12 | Rectifier module | Eton | APR24-3G |
MODEL | 1 Controller + 2 Rectifiers | 1 Controller + 3 Rectifiers | |
Part number | CTOS0201.xxx | CTOS0301.xxx | |
INPUT DATA | |||
Voltage (maximum) | 100 - 250VAC | 100 - 250VAC | |
Mains Configuration (individual feed) |
230VAC, 1 phase or 2 x 1phase |
230VAC, 3 x 1 phase or 3 phase() 230/400VAC, 3 phase (Y) |
|
Mains Connection | 2.5mm2 Terminal blocks, rear connection | ||
Frequency | 45 to 66Hz | ||
OUTPUT DATA | |||
Voltage | 48Vdc | 48Vdc | |
Max. Current | 40A | 100A | |
BATTERY DISTRIBUTION |
|||
LVBD |
Default |
Default |
|
Breaker (Plug-in type) maximum size |
2 x 40A1) |
2 x 80A1) |
|
Connection (rear) | 16mm2 Terminal blocks | M6 cable lug | |
LOAD DISTRIBUTION | |||
Rear connections |
N/A |
2 x 80A, M6 cable lug | |
Rear cabel entry, front access Connections, screw terminals Optional LVLD | 7 x 30A MCB 2) 7 X 4mm2 on MCB 1 and 2 |
N/A | |
Front connections Plug-able screw terminals |
4 x 30A MCB / 7 x 15A Fuse 4mm2 |
N/A | |
CONTROL & MONITORING | |||
Smartpack S | 6x Input/Output and Ethernet, See Smartpack S datasheet | ||
MECHANICAL DATA | |||
Dimensions (W/H/D) | 19"/1U/262mmRecommended minimum cabinet depth, 300 mm | ||
Weight, including controller and distributions, excluding rectifiers |
5.3 kg [11.7 lbs] |
5.2 kg [11.5 lbs] |
|
DESIGN STANDARDS | |||
Electrical safety | UL 60950-1, EN 60950-1 | ||
EMC | ETSI EN 300 386 V.1.4.1 EN 61000-6-1 (immunity, light industry) EN 61000-6-2 (immunity, industry) EN 61000-6-3 (emission, light industry) EN 61000-6-4 (emission, industry) |
||
Environment | ETSI EN 300 019-2-1 Class 1.2 ETSI EN 300 019-2-2 Class 2.3 ETSI EN 300 019-2-3 Class 3.2 |
||
1)See FPS rectifier datasheet for more information |