The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out.
Increasing network speed demands flexible and expandable DC power solutions. The Flatpack2 HE rectifiers are your key building blocks for future needs.
With an efficiency up to 96.5%, the losses have been reduced by 50% compared to the current industry standard. In a global perspective, considering the high energy consumption in the telecom industry, this technology breakthrough is not only reducing operational cost for the operators, but it can also have a significant environmental impact.
Applications
Telecom - mobile / wireless
•radio base stations/ cell sites
•lte / 4g / wimax
•mobile switching center (msc)
•microwave
•broadband telecom - fixed
•central office
•telephony servers / switches
•fiber optics
•microwave
•broadband
•datacenters
power utilities
•scada
Key features
•proven reliability
•high efficiency (he)
•power dense, up to 33 w/inch3
•wide temperature range
•application flexibility 2kw
•global compliance (ce, ul)
•patented he technology
Flatpack2 48v he rectifiers doc 24111x.105.Ds3 - v6.1
Model | 48V / 2000W HE | 48V / 3000W HE | |
Part number | 241115.105 | 241119.105 | |
INPUTDATA | |||
Voltage (nominal) | 185 - 275 VAC / 185 - 275 VDC | 176 - 277 VAC | |
Voltage (range) | 85 - 300 VAC / 85 - 275 VDC | 85 - 305 VAC | |
Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz | 45 - 66 Hz | |
Current (maximum) @ nominal input, full load | 11.6 ARMS | 19.2 ARMS | |
Protection | Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC | Fuse in both lines Varistor for transient protectionDisconnect above 305 VAC | |
OUTPUT DATA | |||
Voltage (default) | 53.5 VDC | ||
Voltage (adjustable range) | 43.5 - 57.6 VDC | 43.5 - 583) VDC | |
Power (maximum) | 2000 W | 3000 W | |
Power @ 85 VAC | 850 W | 1380 W | |
Current (maximum) @ nominal input, full load | 41.7 A | 62.5 A | |
Ripple, 30MHz bandwidth | < 100 mVpp | < 150 mVpp | |
Psophometric noise | < 2 mVRMS | < 2 mVRMS | |
Static Voltage regulation | ±0.5% for 10 - 100% load | ||
Dynamic Voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms | ||
Protection | Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting | ||
OTHER SPECIFICATIONS | |||
Efficiency @ nominal input | 96 % | ||
Isolation | 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth | ||
Alarms: Red LED 'on' | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure | ||
Warnings: Yellow LED 'on' | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage | ||
Normal (module running): Green LED 'on' | |||
Acoustic noise, full load @ Tambient = 25°Cfull load @ Tambient = 40°C | < 20 dBA< 56 dBA | < 40 dBA< 58 dBA | |
MTBF (Telcordia SR-332 Issue I method III (a)) | >350 000 (@ Tambient : 25 °C) | >300 000 (@ Tambient : 25 °C) | |
Operating temperature | -40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing | ||
Temperature de-rating | >55°C (131°F), 1200W @ 75°C (167°F) | >55°C4) (131°F), 2100W @ 75°C (167°F)4) | |
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | ||
Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs) | ||
DESIGN STANDARDS | |||
Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013 | ||
EMC | EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE | ||
Marine | DNVGL-CG-03392) | - | |
Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised | ||
power derating, maximum 1000W @ 230Vac 16 2/3 Hzonly valid for part number 241115.105M | 57.6V for HW revision ≤ 5 from HW revision 6: shutdown at 95°C with de-rating to~1000W |
1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
7 | Rectifier module | Huawi | R4850N1 | |
8 | Rectifier module | Huawi | R4850G1 | |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
|
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
|
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
|
12 | Rectifier module | Eaton | APR24-3G |