Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
UPS RATING | 0.9 POWER FACTOR |
kVA | 20 / 30 / 40 / 50 / 60 / 80 / 100 / 120 / 160 |
kW | 18 / 27 / 36 / 45 / 54 / 72 / 90 / 108 / 144 |
Efficiency | Up to 98% High-efficiency mode, Up to 92% Double-conversion |
GENERAL | |
Efficiency | Up to 94%>99% with Energy Saver System |
Parallel capability | 6x modules w/o tie cabinet; 8x with tie cabinet |
Audible noise | <65 dBA @ 1 meter |
Altitude (max) | 2000m at 40ºC , 104ºF |
ELECTRICAL INPUT | |
Voltage | 208, 380, 400, 415, 480, 6002 |
Voltage range | +10% / -15%3 |
Frequency range | 55-65 Hz |
Power factor | 0.99 (min) |
Input current distortion | <4.5% (no input filter required) |
Soft start capability | Yes |
Internal backfeed protection | Yes |
Broadcast global support | Yes |
ELECTRICAL OUTPUT | |
Voltage | 2084, 3804, 4004, 4154, 4804, 6005 |
Regulation | ±1% |
Inverter | PWM with IGBT switching |
Voltage THD | <2% (100% linear load); <5% (non-linear load) |
Load power factor range | Down to 0.9pf leading without de-rating |
Heat dissipation (BTU/Hr x 1000/Hr) | 80 kVA, 208V: 23.6 160 kVA, 208V: 47.3 80 kVA, 380-480V: 21.9 160 kVA, 380-480V: 43.8 |
BATTERY | |
Battery types | VRLA, AGM, Gel, Wet, Eaton batteries also available |
Battery voltage | 384-480V |
Temperature compensation | Optional |
Charging method | Advanced battery management |
Heat dissipation | <48 BTU @ full load |
DIMENSIONS AND WEIGHTS | |
40-80 kVA modules | HxWxD: 73.7 x 18.9 x 31.6 in./1872 x 480 x 803 mm; 640 lb./290 kg (208V); 568 lb./258 kg (480V) |
100-160 kVA modules | HxWxD: 73.7 x 35.6 x 31.6 in./1872 x 904 x 803 mm; 1,060 lb./481 kg (208V, 480V) |
CERTIFICATION | |
Safety | UL1778, cUL |
EMC | IEC62040-2 EN50091 Class A (restricted access) |
Surge | ANSI C62, 41 Cat, A&B |
OPTIONAL ACCESORIES | |
Module tie cabinet. External maintenance bypass. |
Integrated distribution cabinet. Isolation transformer. |