Model |
48V / 2000W HE |
Part number |
241115.105 |
INPUT DATA |
Voltage (nominal) |
185 - 275 VAC / 185 - 275 VDC |
Voltage (range) |
85 - 300 VAC / 85 - 275 VDC |
Frequency |
45 - 66 Hz, 15-18.5 Hz1) / 0 Hz |
Current (maximum) @ nominal input, full load |
11.6 ARMS |
Protection |
Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC |
OUTPUT DATA |
Voltage (default) |
53.5 VDC |
Voltage (adjustable range) |
43.5 - 57.6 VDC |
Power (maximum) |
2000 W |
Power @ 85 VAC |
850 W |
Current (maximum) @ nominal input, full load |
41.7 A |
Ripple, 30MHz bandwidth |
< 100 mVpp |
Psophometric noise |
< 2 mVRMS |
Static Voltage regulation |
±0.5% for 10 - 100% load |
Dynamic Voltage regulation |
±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
Protection |
Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting |
OTHER SPECIFICATIONS |
Efficiency @ nominal input |
96 % |
Isolation |
3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth |
Alarms: Red LED 'on' |
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
Warnings: Yellow LED 'on' |
Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage |
Normal (module running): Green LED 'on' |
|
Acoustic noise, full load @ Tambient = 25°C full load @ Tambient = 40°C |
< 20 dBA < 56 dBA |
MTBF (Telcordia SR-332 Issue I method III (a)) |
>350 000 (@ Tambient : 25 °C) |
Operating temperature |
-40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing |
Temperature de-rating |
>55°C (131°F), 1200W @ 75°C (167°F) |
Storage temperature |
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
Dimensions[WxHxD] / Weight |
109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs) |
DESIGN STANDARDS |
Electrical safety |
EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013 |
EMC |
EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE |
Marine |
DNVGL-CG-03392) |
Environment |
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |