Customization: | Available |
---|---|
Output Type: | Multiple |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
This small power dense system is purely based on pluggable breakers and rectifiers and can easily be configured to fit your required application, even in field. The combination of Flatpack S HE rectifiers and Smartpack S controller ensures safe, reliable and environmental friendly operation.
With its shallow depth and flexibility the Flatpack S 2U 2-pole system fits most cabinets and is thereby excellent as replacement unit.
Key features
• Complete system
• Smartpack S controller hot pluggable
• High efficiency rectifiers hot pluggable
• 2-pole battery distribution
• Pluggable breakers
• Optional LVBD
• 2-pole load distribution
• 10 x 20A MCB positions
• Pluggable breakers
• Adv. control and monitoring
• Embedded ethernet port
• 260mm system depth
• Perfect as replacment unit
• 2U height
• Including distribution
• 19" wide
• Fit standard racks and cabinets
• Global approvals
Applications
Railway & metro infrastructure
•control & protection
•signaling
•gsm-r
•safety systems
•communication systems
Power utilities
•control & protection
•scada systems
•emergency lighting
•diesel start applications
Offshore - marine
•safety and automation systems
•communication onboard ships
Specifications
MODEL | FPS 2U/3R 2-POLE 24V | FPS 2U/3R 2-POLE 24V LVBD | ||||
Part number | MFGS0302.001 | MFGS0302.002 | ||||
INPUT DATA | ||||||
Voltage (nominal) | 1)185VAC/DC - 305VAC / 300VDC | |||||
Mains configuration (individual feed) | 230VAC, 3 x 1 phase or 3 phase () 230/400VAC, 3 phase (Y) | |||||
Maximum current | 5,9Arms individual feed / 17,7Arms single feed | |||||
Mains connection | 4mm2 terminal blocks, rear connection | |||||
Frequency | 45 - 66Hz | |||||
OUTPUT DATA | ||||||
Nominal Voltage | 24VDC | |||||
Maximum current (total) | 125ADC | |||||
Maximum current distribution (total) | 100ADC | |||||
BATTERY DISTRIBUTION | ||||||
Breaker, 2-pole pluggable D-frame | 1 x 100Amax | |||||
LVBD | N/A | Default | ||||
Connection (rear) | M6 studs (25mm2) | |||||
Battery fuse alarm | Auxiliary switch | |||||
LOAD DISTRIBUTION | ||||||
Breakers, 2-pole pluggable B-frame | 10 x 20Amax | |||||
Connection (rear) | Screw terminals (10mm2) | |||||
Load fuse alarm | Auxiliary switch | |||||
BULK OUTPUT | ||||||
Protection Unfused | ||||||
Connection (rear) M6 Studs (25mm2) | ||||||
CONTROL & MONITORING | ||||||
Smartpack S | 6 x Input / Output and Ethernet2) | |||||
OTHER SPECIFICATIONS | ||||||
Temperature | Operating: -40 to + 65°C full / +85°C derated Storage: -40 to + 85°C | |||||
Coding | Coding to prevent insertion of incorrect power module | |||||
Dimensions (W x H x D) | 482,5 x 89 x 250mm | |||||
Mounting | 19" Flush mount | |||||
Cooling | 30mm space in front and back required for air flow | |||||
Weight (without rectifiers and breakers) | Approx. 7kg | |||||
DESIGN STANDARDS | ||||||
Electrical safety | UL 60950-1, EN 60950-1, CSA C22.2 | |||||
EMC | ETSI EN 300 386 V.1.6.1 EN 61000-6-1 / -2 / -3 / -4 FCC Part 15 Subpart 109 |
|||||
Environment | ETSI 300 019-2 -1 Class 1.2 ETSI 300 019-2 -1 Class 2.3 ETSI 300 019-2 -1 Class 3.2 |
|||||
See Flatpack S datasheet for details; See Smartpack S datasheet for details |
1 | Rectifier module | Emerson /Vertiv | R48-1800A | ![]() |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | ![]() |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | ![]() |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | ![]() |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | ![]() |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | ![]() |
7 | Rectifier module | Huawi | R4850N1 | ![]() |
8 | Rectifier module | Huawi | R4850G1 | ![]() |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
![]() |
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
![]() |
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
![]() |
12 | Rectifier module | Eton | APR24-3G | ![]() |