Model | 48/3000 SHE |
Part number | 241119.106 |
INPUT DATA | |
Voltage (nominal range) | 206 - 264 VAC |
Voltage (operating range) | 85 - 264 VAC |
Frequency | 45 - 66 Hz |
Maximum current | 16 ARMS |
Protection | Fuse in Live, varistor for transient protection, shutdown when VIN is out of range |
OUTPUT DATA | |
Voltage (default) | 53.5 VDC |
Voltage (adjustable range) | 43.21) - 57.6 VDC |
Max power, nominal input | 3000 W |
Max power, de-rated @VIN = 85 VAC | 1000 W |
Max current, @VOUT = 48 VDC | 62.5 A |
Current sharing | ±5.0% of max current |
Static voltage regulation (10-100% load) | ±0.5% |
Dynamic voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
Hold up time (3000W load) | >10ms; output voltage > 42 VDC |
Ripple | <150 mVPP , 30 MHz bandwidth |
Protection |
Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, fuse |
OTHER SPECIFICATIONS | |
Peak Efficiency | 97.8 % |
Isolation |
3.0 kVAC - input to output 1.5 kVAC - input to protective earth 0.5 kVDC - output to protective earth |
Alarms (Red LED) |
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
Warnings (Yellow LED) |
Rectifier in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage |
Normal (Green LED) | Input and output ok |
MTBF (Telcordia SR-332 Iss.3 method II Case L1) | 1 900 000 hours |
Operating temperature (5 - 95% RH non-cond.) | -40 - 75°C [-40 - 167°F ] |
Max output power de-rates above temp / to | 45°C [+113°F] / 1800 W 2) |
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
Dimensions[WxHxD] / Weight | 109 x 41.0 x 327mm [4.25 x 1.61 x 13"] / 2.050 kg [4.5lbs] |
DESIGN STANDARDS | |
Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014 |
EMC | EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019 ETSI EN 300 386 V.2.1.1, FCC CFR 47 Part 15:2013 |
Environment |
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |
1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
7 | Rectifier module | Huawi | R4850N1 | |
8 | Rectifier module | Huawi | R4850G1 | |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
|
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
|
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
|
12 | Rectifier module | Eaton | APR24-3G |