Customization: | Available |
---|---|
Usage: | Telephone, Computer, Workstation, Server |
Type: | Wired |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Type | R48100G1 | |
Basic Specifications |
Dimension | 238 mm(W) × 378 mm(D) × 43 mm(H) |
Weight | ≤ 6.0 kg | |
Cooling | Forced air cooling (Built-in fan) | |
Input Feature |
Input Voltage | 260 to 530 Vac |
AC Input Mode | 380 Vac three-phase three-line | |
Frequency | 45 to 66 Hz, rated: 50/60 Hz | |
Maximum Input Current | ≤ 13 A | |
Power Factor | ≥ 0.99 (Vin: 360 Vac, 380 Vac, 415 Vac, three-phase balance) | |
THD | ≤ 5% (Vin: 308 to 480 Vac) | |
Output Feature |
Efficiency | > 96% Max |
Output Voltage | 43.2 to 58 Vdc, rated voltage: 53.5 Vdc | |
Output Power | 6000W (304 to 530 Vac ) | |
Ripple and Noise | < 200 mV pk-pk, 20 M bandwidth, < 2 mV rms psophometric | |
Hold-up Time | > 10 mS at 6000 W , output voltage > 42 V | |
Output Regulated Voltage Precision | ≤ 0.6% Vo from no load to full load | |
Current Share | ±5% output rated current from 10% to 100% load | |
Environmental Specifications |
Operating Temperature | -33 ºC to +75 ºC (non-derating below 45 ºC), ETS EN 300-019 |
Storage Temperature | -40 ºC to +75 ºC; ETS EN 300-019 | |
Relative Humidity | 5% to 95% (non-condensing), ETS EN 300-019 | |
Altitude Range | ≤ 4000 m (If the altitude is within the range of 2000 m to 4000 m, the maximum operating temperature decreases by 1ºC as the altitude increases by 200 m) | |
Protection |
Input Overvoltage Protection | Protection point: 530 to 550 Vac |
Input Under-voltage Protection | Protection point: < 260 Vac | |
Output Over-voltage Protection | 58.5 to 60.5 Vdc (can be set by monitoring unit) | |
Output Short Circuit Protection | A long term short circuit is allowed. After the fault is rectified, the rectifier will restore automatically | |
Over-temperature Protection | Protection point: > 75 ºC | |
Reliability | MTBF | ≥ 500,000 hours (Telcordia SR-332 issue2 Method 1 at 25 ºC) |
Audible Noises | Specification | ≤ 45dB (25 ºC, full load); sound presure@1m distance, ISO3744 |
Safety/EMC/ Lightening Protection |
Safety Certification | Passed TUV, CE, UL certifications; got the CB certificate; complies with UL60950-1, IEC60950-1, EN60950-1, CAN/CSA C22.2 No. 60950 -1 |
Isolation | Input to output: 4242 Vdc; input to earth: 2121 Vdc; output to earth: 707 Vdc | |
EMC | EN55022 Class B, EN55024, EN61000-3-2, EN61000-3-3, ETSI EN300 386, ETSI EN301489, ITU-T K.20 | |
Lightening protection | Common model (input to earth) / differential model (input to input): 5KA (8/20uS, ITU-T K.44) |
1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
7 | Rectifier module | Huawi | R4850N1 | |
8 | Rectifier module | Huawi | R4850G1 | |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 |
|
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 |
|
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 |
|
12 | Rectifier module | Eaton | APR24-3G |