• Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2

Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2

Usage: Telephone, Computer, Workstation, Server
Type: Wired
Support Network: Ethernet
Information content: Data
Certification: CE, ISO, RoHS
Condition: New
Customization:
Gold Member Since 2020

Suppliers with verified business licenses

Rating: 5.0/5
Hubei, China
to see all verified strength labels (15)

Basic Info.

Model NO.
241119.825
Maximum Current
18.2 Arms
Power
3000 W
Power @ 85 VAC
1200 W
Hold up Time
> 20 Ms
Transport Package
Carton Box
Specification
Brand New
Trademark
Eltek
Origin
Wuhan
Production Capacity
1000 Sets/Month

Product Description

Eltek Flatpack2 380V Rectifier 380/3000 HE Doc 241119.825. DS3 - v3.2

 

Key Features

 

Power Density - 33 w/Inch3

High Efficiency - 96.2%

Or-Ing Protection On Output

Hot Pluggable - Mttr < 5 Min

Voltage Keying

 

Applications

 

DATA CENTER

Centralized battery back-up systems

TELECOM

Central office / large switch sites OTHER INDUSTRIES

380VDC UPS

 

Overview

 

HE rectifier for 380VDC in data centers

The Flatpack2 380/3000 HE rectifier has high efficiency, ORing protection on output and high output power.

Distribute pure battery backup DC voltage with a minimum of loss. Remove the low reliability DC-AC step in the central backup power system and maximize its reliability and efficiency.

Stack cabinets with up to 72 rectifiers to build large power systems monitored by the Smartpack2 controller.

 

Specifications

 

Model Flatpack2 380/3000 HE
Part number 241119.825
INPUT DATA
Voltage (nominal) 176 - 277 VAC
Voltage (range) 85 - 305 VAC
Frequency 45 - 66 Hz
Current (maximum) @ nominal input, full load 18.2 ARMS
Power Factor > 0.99 at 50% load or more

 

Protection

Fuse in L & N Varistor

Disconnect when VIN is out of range

OUTPUT DATA
Voltage (default) 381 VDC
Voltage (adjustable range) 300 - 400 VDC
# Pb cell supported 156 - 168 1)
Power (maximum) 3000 W
Power @ 85 VAC 1200 W
Current (maximum) @ nominal input, full load 9 A (@VOUT < 336 VDC) / 7.9 A (@ VOUT = 381 VDC)
Current sharing (10 - 100% load) ±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±5.0% for 10-50% or 50-10% load variation, regulation time < 25 ms
Hold up time > 20 ms; output voltage > 300 VDC at 1500 W load
Ripple < 1000 mVP-P , 30 MHz bandwidth

 

 

Protection

Overvoltage shutdown

Hot plug-in - Inrush current limiting ORing diode

Short circuit proof High temperature protection

OTHER SPECIFICATIONS
Efficiency @ 230 VAC input > 96.2%
Isolation

3.0 kVAC - input to output, 1.5 kVAC - input to earth, 1.5 kVDC - output to earth,

3.0 kVAC - CAN to primary, 3.0 kVAC - CAN to secondary

Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED) Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED) Input and output ok
Acoustic noise, at nominal input and full load < 40dBA @Tambient< 25°C / <58dBA @ Tambient> 40°C
MTBF (Telcordia SR-332 Issue I method III (a)) >400 000 (@ Tambient : 25 °C)
Operating temperature

-40 to +75°C (-40 to +167°F), humidity 5 - 95% RH non-condensing

Output power de-rates linear from 3000W @ 50°C (122°F) to 980W @ 75°C(167°F)

Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327 mm (4.25 x 1.69 x 13") / < 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011, IEC 60950-1:2005+A1:2009, UL 60950-1:2011, CSA C22.2 No. 60950-1-07
EMC

EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011, EN 300

386:v1.6.1, FCC CFR 47 Part 15:2013

Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2) 2011/65/EU (RoHS) & 2008/98/EC (WEEE)
1) for 156 cells minimum test voltage is 1.923 V/cell. For 168 cell maximum boost voltage is 2.38 V/cell

 

 

Smartpack2 system controller

Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
 

72 rectifiers power cabinet
Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
 

Hotsale Modules

1 Rectifier module Emerson /Vertiv R48-1800A Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
2 Rectifier module Emerson /Vertiv R48-2000A3 Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
3 Rectifier module Emerson /Vertiv R48-2900U Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
4 Rectifier module Emerson /Vertiv R48-3000e3 Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
5 Rectifier module Emerson /Vertiv R48-3500e Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
6 Rectifier module Emerson /Vertiv R48-5800A Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
7 Rectifier module Huawi R4850N1 Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
8 Rectifier module Huawi R4850G1 Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
9 Rectifier module Eltek Flatpack2 48/2000 HE
241115.105
Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
10 Rectifier module Eltek Flatpack2 48/1000 HE
241122.105
Eltek Flatpack2 380V Rectifier 5g Network Equipment 380/3000 He Doc 241119.825. Ds3 - V3.2
11 Rectifier module Eltek Flatpack2 48/3000 HE
241119.105
 
12 Rectifier module Eaton APR24-3G  

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now